71
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
frequency
A0.08
A0.13
Torque boost
0.0%Auto), 0.1%~30.0%
0.1%
0.0%
0~300
Group A1Start and stop parameters
A1.00
Starting mode
0 Start from the starting
frequency
1 Brake first and then start
2 Start on the fly(including
direction judgement), start at
starting frequency
1
0
×
0~2
A1.01
Starting frequency
0.00~60.00Hz
0.01Hz
0.00Hz
0~6000
A1.02
Holding time of
starting frequency
0.00~10.00s
0.01s
0.00s
0~1000
A1.03
DC injection
braking current at
start
0.0%~100.0% drive’s rated
current
0.1%
0.0
0~1000
A1.04
DC injection
braking
time at start
0.00No action
0.01~30.00s
0.01s
0.00s
0~3000
A1.05
Stopping mode
0Dec-to-stop
1Coast-to-stop
2 Dec-to-stop+DC injection
braking
1
0
×
0~2
A1.06
DC injection
braking initial
frequency at stop
0.00~60.00Hz
0.01Hz
0.00Hz
0~6000
A1.07
Injection braking
waiting time at
stop
0.00~10.00s
0.01s
0.00s
0~1000
A1.08
DC injection
braking current at
stop
0.0%~100.0% drive’s rated
current
0.1%
0.0%
0~1000
A1.09
DC injection
braking time at
stop
0.0No action
0.01~30.00s
0.01s
0.00s
0~3000
A1.10
Restart after power
failure
0:Disable
1:Enable
1
0
×
0~1