72
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
A1.11
Delay time for
restart after power
0.0~10.0s
0.1s
0.0s
0~100
failure
A1.12
Anti-reverse
running function
0Disabled
1Enabled (It will operate at zero
frequency when input a reverse
command)
1
0
×
0~1
A1.13
Delay time of run
reverse/forward
0.00~360.00s
0.01s
0.00s
0~36000
A1.14
Switch mode of
run
reverse/forward
Reserved
0Switch when pass 0Hz
1 Switch when pass starting
frequency
1
0
×
0~1
A1.15
Detecting
frequency of stop
0.00~150.00Hz
0.01Hz
0.10Hz
×
0~15000
A1.16
Action voltage of
braking unit
650~750V
1
720
×
650~750
A1.17
Dynamic braking
0Disable
1Enable
1
0
×
0~1
A1.18
Ratio of working
time of braking
unit to drive’s total
working time
0.0~100.0
0.1
80.0
0~1000
Group A2Frequency setting
A2.00
Auxiliary
reference
frequency selector
0 No auxiliary reference
frequency
1AI1
2AI2
3AI3
4Set by DI (PULSEterminal
5Output by PID process
1
0
0~5
A2.01
Main and auxiliary
reference
frequency
calculation
0+
1-
2 MAX Main reference
Auxiliary reference
1
0
0~3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kinco SV100 Series and is the answer not in the manual?

Kinco SV100 Series Specifications