85
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
automatically.
A8.05
Reset interval
2.0~20.0s/time
0.1s
5.0s
×
20~200
A8.06
Fault locking
function selection.
0:Disable.
1:Enable.
1
0
×
0~1
Group b0:Motor parameters
b0.00
Rated power
0.4~999.9KW
0.1
0
×
4~9999
b0.01
Rated voltage
0~ rated volotage of drive
1
0
×
0~999
b0.02
Rated current
0.1~999.9A
0.1A
Dependent
on drive’s
model
×
1~9999
b0.03
Rated frequency
1.00~1000.00Hz
0.01Hz
Dependent
on drive’s
model
×
100~3000
0
b0.04
Number of
polarities of motor
2~24
1
4
×
2~24
b0.05
Rated speed
0~60000RPM
1RPM
1440RPM
×
0~60000
b0.06
Resistance of
stator
%R1
0.00%~50.00%
0.01%
Dependent
on drive’s
model
×
0~5000
b0.07
Leakage
inductance
%Xl
0.00%~50.00%
0.01%
Dependent
on drive’s
model
×
0~5000
b0.08
Resistance of rotor
%R2
0.00%~50.00%
0.01%
Dependent
on drive’s
model
×
0~5000
b0.09
Exciting
inductance
%Xm
0.0%~2000.0%
0.1%
Dependent
on drive’s
model
×
0~20000
b0.10
Current without
load I0
0.1~999.9A
0.1A
Dependent
on drive’s
model
×
1~9999
b0.11
Auto-tuning
0: Auto-tuning is disabled
1: Stationary auto-tuning (Start
auto-tuning to a standstill motor)
2: Rotating auto-tuning
3:Reserved.
1
0
×
0~3
b0.12
Motor’s overload
20.0%~110.0%
0.1%
100.0%
×
200~1100