EasyManuals Logo

Kinco SV100 Series User Manual

Kinco SV100 Series
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
93
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
C1.09
Proportional gain
KP
0.000~10.000
0.001
2.000
0~10000
C1.10
Integral gain Ki
0.000~10.000
0.001
0.100
0~10000
C1.11
Differential gain
Kd
0.000~10.000
0.001
0.100
0~10000
C1.12
Sampling cycle T
0.01~50.00s
0.01s
0.50s
1~5000
C1.13
Output filter
0.01~10.00s
0.01s
0.05
1~1000
C1.14
Error limit
0.0~20.0%
(Corresponding to close-loop
reference)
0.1%
2.0%
0~200
C1.15
Close-loop
regulation
characteristic
0Positive
1Negative
1
0
×
0~1
C1.16
Integral regulation
selection
0: Stop integral regulation when
the frequency reaches the upper
and lower limits
1: Continue the integral
regulation when the frequency
reaches the upper and lower
limits
1
0
×
0~1
C1.17
Preset close-loop
frequency
0.00~300.00Hz
0.01Hz
0.00Hz
0~30000
C1.18
Holding time of
preset close-loop
frequency
0.0~3600.0S
0.1S
0.0S
×
0~36000
C1.19
Preset close-loop
reference 1
-10.00V ~10.00V
0.01V
0.00V
0~2000
C1.20
Preset close-loop
reference 2
-10.00V ~10.00V
0.01V
0.00V
0~2000
C1.21
Preset close-loop
reference 3
-10.00V ~10.00V
0.01V
0.00V
0~2000
C1.22
Preset close-loop
reference 4
-10.00V ~10.00V
0.01V
0.00V
0~2000
C1.23
Preset close-loop
reference 5
-10.00V ~10.00V
0.01V
0.00V
0~2000
C1.24
Preset close-loop
-10.00V ~10.00V
0.01V
0.00V
0~2000