107
DEC Address
Variable name Description States
Type Read [R]
/Write
[W]
BacNet Modbus BacNet Modbus
22 44 TA1
Time zones setting TA1…TA5 and operating modes of
particular time zones for calendar type K1 and calendar
days Monday-Friday K5+2
Format czas TV Register R/W
23 46 TA2 Format czas TV Register R/W
24 48 TA3 Format czas TV Register R/W
25 50 TA4 Format czas TV Register R/W
26 52 TA5 Format czas TV Register R/W
27 54 ModeA1 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
28 56 ModeA2 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
29 58 ModeA3 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
30 60 ModeA4 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
31 62 ModeA5 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
32 64 ModeA6 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
33 66 TB1
Time zones setting TA1…TA5 and operating modes of
particular time zones for calendar days Saturday-Sunday
K5+2
Format czas TV Register R/W
34 68 TB2 Format czas TV Register R/W
35 70 TB3 Format czas TV Register R/W
36 72 TB4 Format czas TV Register R/W
37 74 TB5 Format czas TV Register R/W
38 76 ModeB1 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
39 78 ModeB2 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
40 80 ModeB3 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
41 82 ModeB4 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
42 84 ModeB5 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
43 86 ModeB6 0: Stop, 1: Eco, 2: Comfort 4: Maximum MSV Register R/W
44 88 _DI1 digital input status reading 1 0 – open, 1 – shorted MSV 1408 R
45 90 _DI2 digital input status reading 2 0 – open, 1 – shorted MSV 1440 R
46 92 _DI3 digital input status reading 3 0 – open, 1 – shorted MSV 1472 R
47 94 _DI4 digital input status reading 4 0 – open, 1 – shorted MSV 1504 R
48 96 _DI5 digital input status reading 5 0 – open, 1 – shorted MSV 1536 R
49 98 _DI6 digital input status reading 6 0 – open, 1 – shorted MSV 1568 R
50 100 Ain_1 Analogue input status reading 1 1V = 256 (22V = 22*256 = 5632 = 0x1600) AV Register R
51 102 Ain_2 Analogue input status reading 2 1V = 256 (22V = 22*256 = 5632 = 0x1600) AV Register R
52 104 PT_1 PT1000 Sensor input reading 1 1°C = 256 (22 °C = 22*256 = 5632 = 0x1600) AV Register R
53 106 PT_2 PT1000 Sensor input reading 2 1°C = 256 (22 °C = 22*256 = 5632 = 0x1600) AV Register R