Forwardflow.actual:
Measured forward flow temperature
Forwardflow.set:
Stored set forward flow temperature
Gradient:
Stored gradient of the heating curve
Roominfluence:
Stored influence of the measured room temperature on the forward flow temperature (in per-
cent)
Pump:
Status of the heating circuit pump (On|Off)
Mixer:
Status of the mixer motor (Off|Open|Closed)
Off: Mixer motor is switched off
Open: Mixer opens, increases the forward flow temperature
Closed: Mixer closes, reduces the forward flow temperature
Selector switch:
Shows the selected operating mode on the analogue control unit or the absence of the device
(Frost|Auto|Day|Night|Missing)
Boiler
Main menu >> Operating state >> Boiler >> Boiler No.
Note: The header shows the current boiler program.
DHWC temp., actual:
Measured temperature on the boiler sensor
Desired DHWC temp.:
Stored desire temperature, up to which the boiler is heated
Boiler pump:
Status of the boiler pump (On|Off)
Request:
Status of the heat request (On|Off)
On: Boiler requesting heat – the combustion is started.
Off: Boiler requesting NO heat.
6.8.3
The commands of the KWB Comfort 3 control
6
Operational state