Maintenance
WARNING
Perform work according to the instructions for operation only! Improper work
can put you in life-threatening situations:
m
Danger of crushing and entanglement through unexpected starting of mech-
anisms
m
Fire, explosion and electric shock risk from open cladding, combustion
chamber door and service cover
m
Asphyxiation risk due to carbonisation gases from smoldering fuel when the
combustion chamber door or service cover is open!
4
Shut the system down (Menu "System ON/OFF").
4
Switch the system off (main switch to "0").
4
Pull the plug and secure the system against being switched on again.
4
Allow the system to cool down. Only open the cladding, combustion cham-
ber door and service cover when the system is cold and de-energised!
Standards for maintenance
The subsequent regulations originate from the Austrian "Technischen Richtlinie für vorbeugen-
den Brandschutz" [TRVB H118] (Technical Guideline for Preventative Fire Protection) – ensure
that you comply with all corresponding local regulations!
Weekly visual inspection
Perform a weekly inspection of the entire system including the
fuel storage room. Immediately
remedy any deficiencies that are found!
Monthly inspections
•
Cleanliness of the flue-gas routes (flue-gas passes in the boiler, adapter and chimney)
• Proper operation of the control … Are alarm messages displayed?
• Functionality of fault alarms and warning device(s);
• Proper operation of the combustion air fan and induced draught fan … Are alarm messag-
es displayed?
• Proper condition of the combustion chamber … Are alarm messages displayed?
In addition also provide for:
• a fire extinguisher that is ready for use and can be carried,
• a boiler room free of flammable materials,
• fully functional fire protection closures (fire protection closures – self-closing),
• legible system stickers, which KWB has provided for safe and correct operation (please
order new stickers if necessary)
Additional regular work
m
Your KWB Easyfire is equipped with an automatic cleaning system. All ash is collected in
the ash container.
4
Empty the
ash container regularly.
7
7.1
7.1.1
7.1.2
7.1.3
7
Maintenance
42
B KWB Easyfire EN, 05.2011