CS102 SNMP Card
User Manual
59
7.2. Managing the UPS Shutdown Schedule
CS102 supports two kinds of shutdown schedules: Weekly Schedule and Special Day
Schedule.
Note: Before managing the UPS Shutdown Schedule, please make sure that the Date and Time
configured in CS102 is correct.
Scenario
Status: Special Day Schedule
Delay (Min): 1 (default value)
1
st
Warning (Sec): 10 (default value)
Warning Interval (sec): 10 (default value)
UPS Shutdown Delay (Sec): 180 (default value)
Shutdown day & time: Monday 22:20:00
Restart day & time: Tuesday 09:00:00
22 : 20 : 00 22 : 23 : 00 Mon 09 : 00 : 00 Tue
UPS ON
UPS SLEEP
UPS OFF