EasyManua.ls Logo

Lenze 8400 BaseLine C - Page 191

Lenze 8400 BaseLine C
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05 191
9 System bus "CAN on board"
9.6 Process data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
The communication parameters such as the transmission mode and cycle time can be set freely for
every PDO and independently of the settings of other PDOs:
Blocking time
In C00324/x
, an "inhibit time" can be set that defines the shortest transmission cycle for the "asyn-
chronous - manufacturer-specific/device-profile specific" transmission type.
Example: Cycle time = 500 ms, blocking time = 100 ms, sporadic data change:
In case of a sporadic data change < 500 ms, fastest transmission is every 100 ms (event-cont-
rolled transmission). The transmission cycle timer is reset to 0 if the transmission has been trig-
gered in an event-controlled manner.
In case of a sporadic data change > 500 ms, fastest transmission is every 500 ms due to the set
blocking time (cyclic transmission).
Tip!
The setting can also be carried out via the following CANopen objects:
I-1400
... I-1401: Communication parameters for RPDO1 ... RPDO2
I-1800
... I-1801: Communication parameters for TPDO1 ... TPDO2
Parameter Info Lenze setting
Value Unit
CAN1_OUT
C00322/1
Transmission mode 254
C00324/2
Blocking time 0 ms
C00356/5
Cycle time 0 ms
CAN2_OUT
C00322/2
Transmission mode 254
C00324/3
Blocking time 0 ms
C00356/2
Cycle time 0 ms
CAN1_IN ... CAN2_IN
C00323/1...2
Transmission mode CAN1_IN ... CAN2_IN
For RPDO, it serves as monitoring setting
in the case of sync-controlled PDOs.
254

Table of Contents

Other manuals for Lenze 8400 BaseLine C

Related product manuals