10 Parameter reference
10.2 Parameter list | C00066
247
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00066
C00073
C00074
C00081
C00084
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load being detected sensorless via a motor model
If the value displayed here exceeds the threshold set in C00120
, the fault message "OC6: Thermal motor overload
(I2xt)" is output and the fault response set in C00606
is executed (default setting: "Warning").
Display range (min. value | unit | max. value)
0 % 200
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00073 | Vp Imax controller
Data type: UNSIGNED_16
Index: 24502
d
= 5FB6
h
Amplification factor Vp for Imax controller
Setting range (min. value | unit | max. value) Lenze setting
0.00 16.00 0.25
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00074 | Ti Imax controller
Data type: UNSIGNED_16
Index: 24501
d
= 5FB5
h
Reset time Ti for Imax controller
Setting range (min. value | unit | max. value) Lenze setting
12 ms 9990 65 ms
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00081 | Rated motor power
Data type: UNSIGNED_16
Index: 24494
d
= 5FAE
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor power for the sensorless vector control (SLVC
).
Setting range (min. value | unit | max. value) Lenze setting
0.00 kW 99.00 11.00 kW
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00084 | Motor stator resistance
Data type: UNSIGNED_32
Index: 24491
d
= 5FAB
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automati-
cally. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
0 mohm 200000 330 mohm
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1