EasyManua.ls Logo

Lenze 8400 BaseLine C - Page 284

Lenze 8400 BaseLine C
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05 284
10 Parameter reference
10.2 Parameter list | C00600
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00600
C00601
C00604
C00606
Parameter | Name:
C00600 | Resp. to DC bus undervoltage
Data type: UNSIGNED_8
Index: 23975
d
= 5DA7
h
Configuration of monitoring of the motor control (group 3)
Selection list
1Fault
2Trouble
Subcodes Lenze setting Info
C00600/1 2: Trouble Response to undervoltage in the DC bus
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00601 | Del. resp.to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Delay times for error responses
Setting range (min. value | unit | max. value)
0.00 s 65.00
Subcodes Lenze setting Info
C00601/1 2.00 s Delay time for error activation "DC-bus overvoltage"
In case of DC-bus overvoltage, an error is only trans-
mitted after this delay time has elapsed.
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (C00123) is reached.
The current device utilisation is displayed in C00064
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload (I²xt)
Data type: UNSIGNED_8
Index: 23969
d
= 5DA1
h
Response if the adjustable motor overload threshold (C00120) is reached.
The current thermal motor load is displayed in C00066
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1