Installation
4-8
SHB9300CRV EN 2.0
l
Observe the following points to comply with the technical data:
Ensure sufficient ventilation of the heat sink.
The free space behind the control cabinet back panel must be at least 500 mm.
l
If several controllers are installed in the control cabinet:
Do not install the controllers on top of each other.
l
The cooling path must not exceed the thermal resistances stated in the table:
Controller Cooling path
Type Power to be dissipated P
loss
[W] R
thmax heatsink
[K/W]
9321-Cx 80 0.50
9322-Cx 80 0.50
9323-Cx 100 0.40
9324-Cx 155 0.25
9325-Cx 210 0.19
9326-Cx 360 0.10
9327-Cx 410 0.09
9328-Cx 610 0.06
l
The temperature of the cold plate must not exceed +85 C.
l
Insertion depth t of the screws into the base plate of the controller:
8mm$ t $ 10 mm
l
For the bore pattern and surface quality of the heatsink please consult the factory.
l
Apply the heat conducting paste (accessory kit) onto the cold plate of the controller.