Basics for wiring according to EMC
Wiring outside the control cabinet
6
Basic unit wiring
6.3
6.3.4
L
6.3-7
EDS82EV903-1.0-11/2002
l
It is possible to connect the controller, mains choke or RFI filter to the mains
via single cores or unshielded cables.
l The cable cross-section must be rated for the assigned fuse protection
(VDE 0160).
(
((
( Stop!
The motor cable is highly susceptible to interference. For this
reason you achieve an optimum wiring on the motor side, if you
l use shielded and low-capacity motor cables only.
l do not incorporate further cables in the motor cable (e.g. for
brake control, external fans etc.).
l shield the cable for temperature monitoring of the motor (PTC
or thermal contact)and separate it from the motor cable.
In special cases it is possible to incorporate the cable for motor temperature
monitoring in the motor cable.
(¶ 6.3-1)
Wiring on the mains side
Wiring on the motor side