10.8 Configuration of analog and digital setpoints and actual values
10.8.1 Setpoint source selection
Fixed setpoint source selection.
l C0001 = 0, 2: Setpoint source as described in the following. Link the
setpoint source with the internal analog signal under C0412.
l C0001 = 1: Setpoint source is the parameter channel of AIF. The freely
configurable signals are switched off (C0412/x = 0 or 255). The setpoint
must be written to the codes which are assigned to the signals (see signal
flow charts or description of C0412).
l C0001 = 3: Setpoint source is the process data channel of AIF. The setpoint
is written to an AIF input word (AIF-IN.W1 or AIF-IN.W2). Link the AIF input
word with the internal analog signal under C0412.
Description