Basic units in the power range 0.25 ... 2.2 kW
Wiring according to EMC (installation of a CE-typical drive system)
6
Basic unit wiring
6.4
6.4.1
L
6.4-3
EDS82EV903-1.0-11/2002
M
3~
PES
L < 500 mmL<40mm
PE
PE
PE
8
9
PES
PES
1
2
3
4
5
6
7
0
58200vec008
Fig. 6.4-1 Wiring in compliance with EMC standards
0
Mounting plate with electrically conductive surface
1
Control cable to function module, connect the shielding to the EMC shield sheet
(PES)withasurfaceaslargeaspossible
2
2-pole terminal for motor PE and motor shield
3
PE of the motor cable
4
Shield of the motor cable
5
Shielded motor cable, low-capacity
(core/core up to 1.5 mm
2
75 pF/m; from 2.5 mm
2
100 pF/m; core/shield
150 pF/m)
6
Shielded PTC cable or thermal contact cable
7
Connect cable shields to the EMC shield sheet (PES) with a surface as large as
possible. Use enclosed clamps.
8
Star or delta connection as indicated on the motor nameplate
9
EMC-cable connector (not included in the delivery package)
Realisation