Code table
10
Function library
10.20
L
10.20-4
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
s
uSEr
(cont.)
Saving of own
settings
9 PAR1 ð Own settings You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. S e t C0003 = 3, a cknowledge with
v
4. S e t C0002 = 9, a cknowledge with v,
to save your own basic settings
5. S e t C0003 = 1, a cknowledge with
v
6. Enable the controller .
C0002*
s
Loading/copying of
your own basic
Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4
uSEr
settings
5 Own settings ð PAR1
Restorage of own basic setting in the
(cont.)
6 Own settings ð PAR2
selected parameter set
7 Own settings ð PAR3
8 Own settings ð PAR4
C0003* Non-volatile 1
0 ParameternotsavedinEEPROM Data loss after mains disconnection
v
parameter saving
1 Parameter always saved in EEPROM • Active after every mains connection
• Cyclic parameter changes via bus
module are not allowed.
3 Own settings saved in EEPROM The parameter set 1 saved as own basic
setting with C0002 = 9
C0004* Bar-graph display 56
1 {Code No.} 989
• Bargraph display indicates the selected
56 = controller l o a d (C0056)
va
ue
n
a
er power on
• Range -180 % ... +180 %