Code table
10
Function library
10.20
L
10.20-13
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0111
v
Configuration
analog output
X3/62 (AOUT1-IN)
Analog signal output to terminal Change of C0111 is copied to
C0419/1.Free configuration in C0419/1
sets C0111 = -255 -!
^ 10.12-4
0
0 Output frequency with slip (MCTRL1-NOUT+SLIP) 6V/12mA C0011
1
Device utilisation (MCTRL1-MOUT) at V/f
characteristic control (C0014 = 2 or 3)
3V/6mA Rated active inverter current
(active current/C0091)
Actual motor torque (MCTRL1-MACT) at vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)
3V/6mA Rated motor torque
2 Apparent motor current (MCTRL1-IMOT) 3V/6mA Rated inverter current
3 DC-bus voltage (MCTRL1-DCVOLT) 6V/12mA DC 1000 V (400 V mains)
6V/12mA
DC 380 V (240 V mai ns)
4 Motor power 3V/6mA Rated motor power
5 Motor voltage (MCTRL1-VOLT) 4.8 V/9.6 mA Rated motor voltage
6 1/output frequency (1/C0050) (MCTRL1-1/NOUT) 2V/4mA 0.5 × C0011
7 Output frequency with limits
(DCTRL1-C0010...C0011)
0 V/0 mA/4 mA f=f
min
(C0010)
6V/12mA
f=f
max
(C0011)
8
Operation with process controller (C0238 = 0, 1):
Act. process controller value (PCTRL1-ACT)
6V/12mA C0011
Operation without process controller (C0238 = 2):
Output frequency without slip (MCTRL1-NOUT)
9 Ready for operation (DCTRL1-RDY)
Selection 9 ... 25 correspond to the digital
C
10 TRIP fault message (DCTRL1-TRIP)
p
g
functions of the re lay output K1 (C0008) or
t
h
e
d
i
g
i
t
a
l
o
u
t
p
u
t
A
1
C
0
1
1
7
11 Motor is running (DCTRL1-RUN)
the digital output
A
1 (C0117):
L
O
W
=
0
V
/
0
m
A
/
4
m
A
12 Motor is running / CW rotation (DCTRL1-RUN-CW)
L
O
W
=
0
V
/
0
m
A
/
4
m
A
HIGH = 10
V
/
20 m
A
13 Motor is running / CCW rotation
(DCTRL1-RUN-CCW)
H
I
G
H
=
1
0
V
/
2
0
m
A
14 Output frequency = 0 (DCTRL1-NOUT=0)
15 Frequency setpoint reached
(MCTRL1-RFG1=NOUT)
16 Value has fallen below frequency t hresho ld Q
min
(f < C0017) (PCTRL1-QMIN)
LOW active
17 I
max
limit reached (MCTRL1-IMAX)
C0014 = - 5- : Torque setpoint reached
18 Overtemperature (J
max
-5°C)
(DCTRL1-OH-WARN)
19 Value has fallen below TRIP or Q
min
or pulse
inhibit (IMP)is active (DCTRL1-TRIP-QMIN-IMP)
20 PTC warning (DCTRL1-PTC-WARN)
21 Apparent motor current < current threshold
(DCTRL1-IMOT<ILIM)
Belt monitoring
Apparent motor current = C0054
22 Apparent motor current < current threshold and
output frequenc y > frequency threshold Q
min
(DCTRL1-(IMOT<ILIM)-QMIN)
p
p
Current t hreshold = C0156
Frequency threshold Q
min
= C0017
23 Apparent motor current < current threshold and
RFG 1: Input = output
(DCTRL1-(IMOT<ILIM)-RFG-I= 0)
24 Warning motor phase failure
(DCTRL1-LP1-WARN)
25 Minimum output frequency reached (f C0010)
(PCTRL1-NMIN)
LOW active
255 Freely configured under C0419/1 Only display
Do not change C0111 since settings under
C0419/1 can be lost