Parameter Name / value range / [default seng] Info
0x2860:001
(P201.01)
Frequency control: Default setpoint source
(Stnd. setpoints: Freq. setp. src.)
Selecon of the standard setpoint source for operang mode "MS:
Velocity mode".
•
The selected standard setpoint source is always acve in the operat-
ing mode 0x6060 (P301.00) = "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 365
1 Keypad The setpoint is specied locally by the keypad.
•
Default seng: 0x2601:001 (P202.01)
•
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1 ^ 409
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2 ^ 413
5 Network The setpoint is dened as process data object via the network.
4Conguring the network ^ 172
11 Frequency preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 373
12 Frequency preset 2
13 Frequency preset 3
14 Frequency preset 4
15 Frequency preset 5
16 Frequency preset 6
17 Frequency preset 7
18 Frequency preset 8
19 Frequency preset 9
20 Frequency preset 10
21 Frequency preset 11
22 Frequency preset 12
23 Frequency preset 13
24 Frequency preset 14
25 Frequency preset 15
31 Segment preset 1 (from version 03.00) For the setpoint selecon, the segment presets parameterised for the
"sequencer" funcon can be selected as well.
4Sequencer ^ 325
32 Segment preset 2 (from version 03.00)
33 Segment preset 3 (from version 03.00)
34 Segment preset 4 (from version 03.00)
35 Segment preset 5 (from version 03.00)
36 Segment preset 6 (from version 03.00)
37 Segment preset 7 (from version 03.00)
38 Segment preset 8 (from version 03.00)
50 Motor potenometer The setpoint is generated by the "motor potenometer" funcon. This
funcon can be used as an alternave setpoint control which is control-
led via two signals: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer setpoint source (MOP) ^ 378
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Commissioning
Parameter seng
Basic inverter sengs
42