Parameter Name / value range / [default seng] Info
0x2860:001
(P201.01)
Frequency control: Default setpoint source
(Stnd. setpoints: Freq. setp. src.)
Selecon of the standard setpoint source for operang mode "MS:
Velocity mode".
The selected standard setpoint source is always acve in the operat-
ing mode 0x6060 (P301.00) = "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 365
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:001 (P202.01)
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1 ^ 409
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2 ^ 413
5 Network The setpoint is dened as process data object via the network.
4Conguring the network ^ 172
11 Frequency preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 373
12 Frequency preset 2
13 Frequency preset 3
14 Frequency preset 4
15 Frequency preset 5
16 Frequency preset 6
17 Frequency preset 7
18 Frequency preset 8
19 Frequency preset 9
20 Frequency preset 10
21 Frequency preset 11
22 Frequency preset 12
23 Frequency preset 13
24 Frequency preset 14
25 Frequency preset 15
31 Segment preset 1 (from version 03.00) For the setpoint selecon, the segment presets parameterised for the
"sequencer" funcon can be selected as well.
4Sequencer ^ 325
32 Segment preset 2 (from version 03.00)
33 Segment preset 3 (from version 03.00)
34 Segment preset 4 (from version 03.00)
35 Segment preset 5 (from version 03.00)
36 Segment preset 6 (from version 03.00)
37 Segment preset 7 (from version 03.00)
38 Segment preset 8 (from version 03.00)
50 Motor potenometer The setpoint is generated by the "motor potenometer" funcon. This
funcon can be used as an alternave setpoint control which is control-
led via two signals: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer setpoint source (MOP) ^ 378
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Commissioning
Parameter seng
Basic inverter sengs
42