4 PROFINET
Diagnostics
12 Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015
I&M2 Installation date (*)
Defines the I&M2 Installation date of the I/O device.
I&M3 additional information (*)
Defines the I&M3 Additional information of the I/O device.
Defines the I&M4 Signature code of the I/O device.
4.3 Diagnostics
Active settings can be checked in the Parameters listed below:
-- ... [Actual value] ... --
Displays the active IP address of the I/O device.
-- ... [Actual value] ... --
Displays the active subnet mask of the I/O device.
-- ... [Actual value] ... --
Displays the active gateway address of the I/O device.
-- ... [Actual value] ... --
Displays the active station name of the I/O device.
-- ... [Actual value] ... --
Displays the MAC address of the I/O device.
Bit # description:
0: Initialized
1: Online
2: Connected
3: IP address error
4: Hardware fault
6: Watchdog elapsed
7: Protocol error
Displays the bus status of the I/O device.
0: No error
2: Unit ID unknown
3: Max. units exceeded
4: Invalid size
5: Unit type unknown
6: Runtime plug
7: Invalid argument
8: Service pending
9: Stack not ready
10: Command unknown
11: Invalid address descriptor
Displays the bus error1 of the I/O device.
Bit # description:
7: IP address error
8: Station name problem
9: DataExch left
10: Stack boot error
11: Stack online error
Displays the bus error2 of the I/O device.