6 EtherNet/IP
EtherNet/IP quick start
34 Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015
6.5.3 Compatibility with Other Products
The i500 EtherNet/IP module is a CIP slave adapter and can be controlled by any CIP Generic master capable of
either class 1 or class 3 messaging.
6.6 EtherNet/IP quick start
1. Set the IP address, Subnet and Gateway of the inverter with Parameter 0x23A1:XX and the Rotary Switch
2. For network control the following setup needs to be done:
- Set 0x2631:37 (P400:37 )“Network enable” to P400:37 to 114 Network ControlEnableRequest.Bit”
- Set 0x2860:1 (P201:1) “Default frequency setpoint” to “Network Frequency Setpoint” [5].
3. Save the parameter with 0x2022:3 (P700:3) and power cycle the drive completely that the configuration
takes effect.
4. Configuring the Network Master
Master Support Files
Some EtherNet/IP master configuration software utilizes Electronic Data Sheet (eds) files to configure the
network profile and communications with the relevant devices. Some use this file for automatic tag genera-
tion. The iSeries eds file is available on the Lenze website.
Note: AB controllers do not require the eds file to add the drive to their configuration.
5. For cyclic data exchange / acyclic data exchange refer to the sections above.
6.7 Cyclic Data Access (Implicit Messaging)
To map the drive to an EtherNet/IP scanner in RSLogix 5000 for implicit messaging
Implicit Messaging:
1. Click the [I/O Configuration] folder in the left-hand navigation window
2. Click the appropriate Ethernet Port folder, [1769-L32E Ethernet Port] in this example.
3. Right click on the [Ethernet] network icon and select [New Module] under the Ethernet port of the Control-
ler's EtherNet/IP scanner.
Note: The project in RSLogix 5000 must be in the offline state to add the drive to the configuration.