2 Device Overview
Rotary Selector (EtherNet/IP, EtherCAT only)
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 7
2.2 Rotary Selector (EtherNet/IP, EtherCAT only)
The two rotary selectors can select a hexadecimal number in the range of 0x00 to 0xFF (= 0…255). They configure
the last part of the device IP address (EtherNet/IP) or Identifier (EtherCAT).
Rotary Switch
Fig. 2: Rotary Switches
EtherNet/IP
Rotary selector setting
Description
0x00
Use unmodified value configured in IP address parameter
0x01…0xFE
Use IP address value configured in IP address and overwrite last byte with selected
value
0xFF
Set default IP address
The configured value is applied on next device restart or on network restart command 0x23A0:0 (P508:0).
EtherCAT
Rotary selector setting
Description
0x00
Use value configured in identifier parameter
0x01…0xFF
Use this value as identifier
The value is immediately valid
The configured value is applied on next device restart or on network restart command 0x2360:0 (P508:0).
Adress/Identifier setting:
EtherNet/IP IP address: 0x23A1:1 (P510:1)
EtherCAT Identifier: 0x2361:4 (P510:4)
Active Adress/Identifier:
EtherNet/IP IP address: 0x2382:1 (P511:1)
EtherCAT Explicit device identifier: 0x2362:4 (P511:4)
0xn0 0xn