2 Device Overview
Rotary Selector (EtherNet/IP, EtherCAT only)
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 7
2.2 Rotary Selector (EtherNet/IP, EtherCAT only)
The two rotary selectors can select a hexadecimal number in the range of 0x00 to 0xFF (= 0…255). They configure
the last part of the device IP address (EtherNet/IP) or Identifier (EtherCAT).
Rotary Switch
Fig. 2: Rotary Switches
EtherNet/IP
Use unmodified value configured in IP address parameter
Use IP address value configured in IP address and overwrite last byte with selected
value
The configured value is applied on next device restart or on network restart command 0x23A0:0 (P508:0).
EtherCAT
Use value configured in identifier parameter
Use this value as identifier
The value is immediately valid
The configured value is applied on next device restart or on network restart command 0x2360:0 (P508:0).
Adress/Identifier setting:
EtherNet/IP IP address: 0x23A1:1 (P510:1)
EtherCAT Identifier: 0x2361:4 (P510:4)
Active Adress/Identifier:
EtherNet/IP IP address: 0x2382:1 (P511:1)
EtherCAT Explicit device identifier: 0x2362:4 (P511:4)