7 Drive Profile
NETword Configuration
56 Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015
7.4 NETword Configuration
Instead of using the predefined command and status word there are general NETWords can be configured.
i
Depending on the fieldbus the mapping can be done in the Slave (inverter) or in the Master (PLC).
Note: If the mapping is done in the Master (Example: PROFIBUS) the mapping in the Slave is overwritten!
Master Inverter (NETWordIn)
NETWordIn1: Function trigger bit
Value: 0x4008:1 (P590:1)
Configuration: 0x400E:1 (P505:1-16)
NETWordIn2: Switch digital outputs/relay
Value: 0x4008:2 (P590:2)
Configuration: 0x2643:1-3 (P420:1-3)
NETWordIn3: Source for AO1/AO2
Value: 0x4008:3 (P590:3)
Configuration AO1: 0x2639:2 (P440:2)
Configuration AO1: 0x263A:2 (P441:2)
NETWordIn4: Source for AO1/AO2
Value: 0x4008:4 (P590:4)
Configuration AO1: 0x2639:2 (P440:2)
Configuration AO1: 0x263A:2 (P441:2)
Inverter Master (NETWordOut)
NETWordOut1: Drive Status bits
Value: 0x400A:1 (P591:1)
Configuration: 0x2635:10-25 (P420:10-25)
NETWordOut2: Switched by Sequencer
Value: 0x400A:2 (P591:2)
Configuration: Sequencer parameter