6 EtherNet/IP
EtherNet/IP Connection to Engineering Tools
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 43
Torque control mode is not implemented in inverter SW version 2.0
6.9 EtherNet/IP Connection to Engineering Tools
1. Power the device externally either by mains or external 24V supply and connect the inverter to the PC using
the USB diagnostic adapter.
2. Set address and station name:
The station name, the IP address, subnet mask, and gateway address can either be assigned by the PLC-
controller via EtherNet/IP or set manually in the Easy Starter.
If the settings are done with Easy Starter set the following parameters:
a. Communication parameters:
Name Parameter Default:
IP Address 0x23A1:1 (P510:1) 192.168.124.16
Subnet 0x23A1:2 (P510:2) 255.255.255.0
Gateway 0x23A1:3 (P510:3) 0.0.0.0
Save the parameter with 0x2022:3 (P700:3) and power cycle the drive that the configuration takes
effect.
3. Connect the PC to the i500 EtherNet/IP with an Ethernet cable.
4. Set the IP address of the network adapter in your PC to the same range than the inverter IP address.
Example:
IP Address 192.168.124.1
Subnet 255.255.255.0
Select the connection “Ethernet” in the Easy Starter
Set the correct IP address of the device and add it. Now the objects of the inverter are accessible in Easy
Starter.