3 Fieldbus General
Status LED
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 9
3 Fieldbus General
Enable Network
In order to control the drive from the network the 0x2631:37 (P400:37) Network enable needs to be set (Either
setting “TRUE” or mapping to a digital input to trigger signal). Once it is asserted the drive enters the network
control mode.
It is important to note that in network control mode the following functions still are active:
0x2361:1 (P400:1) Inverter Enable, 0x2361:1 (P400:2) Run/Stop 0x2361:3 (P400:3) Quick Stop, 0x2361:4
(P400:4) Reset fault, 0x2361:1 (P400:5) DC Brake
All other function triggers are disabled while the drive is in the network control mode.
0:Not connected
(Reference see P400:1)
Enables the network for control
State:
TRUE: Network is enabled
FALSE: Network is disabled
Note:
If Network is enabled (Network enable 0x2361:37, P400:37 is HIGH) it is
not mandatory that Inverter enable (0x2361:1, P410:1) or Run/Stop
(0x2361:2, P410:2) are assigned to a digital input (DI1-7).
They can be set to [1] Constant TRUE to Enable and Run the inverter
without using digital inputs (DI1-7).
Several command words, status and setpoint are available to control the drive from remote:
CIA402 (Predefined mapping) Used for EtherCAT/CAN
AC drive profile (Predefined mapping) Used for EtherNet/IP
Lenze Legacy (Predefined mapping)
Netword IN/Out (Configurable mapping)
See chapter 7 Drive Profile for details.