6 EtherNet/IP
Diagnosis
30 Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015
6.3 Diagnosis
Active settings can be checked in the Parameters listed below:
-- ... [Actual value] ... --
Current EtherNet/IP address settings
-- ... [Actual value] ... --
Current EtherNet/IP Subnet mask
-- ... [Actual value] ... --
Current EtherNet/IP Gateway Address
-- ... [Actual value] ... --
-- ... [Actual value] ... --
Current Multicast address settings
-- ... [Actual value] ... --
Displays the setting of the EtherNet/IP module's address switch.
0:Software Setting from IP configuration
1-254:IP address - XXX.XXX.XXX.[SWITCH]
255:Factory Default of communication objects
0: Not connected
1: 10Mbps/Half Duplex
2: 10Mbps/Full Duplex
3: 100Mbps/Half Duplex
4: 100Mbps/Full Duplex
0: Not connected
1: 10Mbps/Half Duplex
2: 10Mbps/Full Duplex
3: 100Mbps/Half Duplex
4: 100Mbps/Full Duplex
-- ... [Actual value] ... --
Display of current CIP module status info
-- ... [Actual value] ... --
Display of current CIP network status
6.4 Error and Error Reaction
Implicit Messaging Timeout
Class 1 connections are monitored by watchdog timeout given in the forward open command while establishing a
connection. Reaction is defined in 0x2859:1.
Explicit Messaging Timeout
To support controllers that are not capable of class 1 connections the iSeries drive supports the watchdog on
class 3 connection messages and in addition an overall EtherNet/IP timeout on unconnected services 0x23A1:10.
For a connected class 3 connection the timeout is configured by the client, the reaction within the drive can be
set in 0x2859:6.