7 Drive Profile
Legacy Lenze Format
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 51
7.2.2 Status word
0x400C:2 P593:2 Lenze Legacy C150 status word
Bits
Function
Comments
0
Active Parameter Set
0 = Parameter Set 1 or 3 active
1 = Parameter Set 2 or 4 active
1
Power stage inhibited
0 = enabled
1 = inhibited
2
Current/torque limit reached
Current limit reached
Torque limit reached (in Torque mode)
3
Frequency setpoint reached
4
Ramp generator
Input = Output
5
Below Frequency threshold
Below Frequency threshold Qmin Index 0x4005
(f < 0x4005) Qmin
6
Actual frequency = 0
7
Inhibit (1-activ/0-inactiv)
0 = Drive Enabled
1 = Drive Inhibited
8
Encode status bit 0
0000 = Initializing
0001 = Mains Voltage Off
0010 = Switch n Inhibited
0011 = Operation Inhibited
0100 = Flying Restart
0101 = DC Brake Active
0110 = Operation Enabled
0111 = Message Active
1000 = FAULT
9
Encode status bit 1
10
Encode status bit 2
11
Encode status bit 3
12
Over-temperature warning
13
DC Bus overvoltage
14
Rotation (0-CW/1-CCW)
15
Ready for Operation