Inverter i550-C5.5/400-3 i550-C7.5/400-3 i550-C11/400-3 i550-C15/400-3
Cable installaon in compliance with EN 60204-1
Laying system B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL gR
Max. rated current A 25 32 32 63
Circuit breaker
Characteriscs B
Max. rated current A 25 32 32 63
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL gR
Max. rated current A 25 32 32 63
Circuit breaker
Characteriscs B
Max. rated current A 25 32 32 63
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Mains connecon
Connecon X100
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5
Max. cable cross-secon mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Motor connecon
Connecon X105
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5
Max. cable cross-secon mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Technical data
3-phase mains connecon 480 V
Fusing and t
erminal data