Inverter i550-C18/400-3 i550-C22/400-3 i550-C30/400-3 i550-C37/400-3
Cable installaon in compliance with EN 60204-1
Laying system B2 C
operaon without mains choke
Fuse
Characteriscs gR -
Max. rated current A 63 63 - -
Circuit breaker
Characteriscs B -
Max. rated current A 63 63 - -
operaon with mains choke
Fuse
Characteriscs gR
Max. rated current A 63 63 80 100
Circuit breaker
Characteriscs B
Max. rated current A 63 63 80 100
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Mains connecon
Connecon X100
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5 10
Max. cable cross-secon mm² 35 50
Stripping length mm 18 19
Tightening torque Nm 3.8 4
Required tool 0.8 x 5.5 Allen key 4.0
Motor connecon
Connecon X105
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5 10
Max. cable cross-secon mm² 35 50
Stripping length mm 18 19
Tightening torque Nm 3.8 4
Required tool 0.8 x 5.5 Allen key 4.0