Implemented CANopen objects
Overview
I−1011: Restore default parameters
13
l
102
EDSMF2178IB EN 3.0
13.2.11 I−1011: Restore default parameters
Loading of Lenze settings
) Note!
For this function, the subindices to be used depend on the controller type.
Index (hex)
0x1011
Name
Restore default parameters
Subindex Default
setting
Value range Access Data type
0
Restore default
parameters
0 ... 2
32
− 1
ro U32
1
rw U32
...
7
Subindices
Subindex Authorisati
on
Description
Write Read
0roWhile writing, the 0x06010002 error
message occurs.
Max. available subindex (depending on
standard device):
l 93xx : 3
l ECSXX: 3
l 82vector : 7
l 82xx: 5
1
rw
All parameters can be loaded
2
This function is not supported.
While writing, the 0x08000020 error
message occurs.
Only object communication parameters
can be loaded
3 Only manufacturer−specific parameters
can be loaded
(Index 0x6000 ... 0x9FFF)
4 Parameter set 1 can be loaded
5 Parameter set 2 can be loaded
6 Parameter set 3 can be loaded
7 Parameter set 4 can be loaded