Technical data
Rated data
Operation with increased power at a 230 V mains
4
56
EDS84ASC552 EN 10.0
Fuses and cable cross-sections
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 - Laying system L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVxxx2512 C 6 6 1 - - 6 18 30
3)
E84AVxxx3712 - - - - - 10 16
E84AVxxx5512 C10 10 1.5 - - 10 16 30
3)
E84AVxxx7512 - - - - - 15 14
E84AVxxx1122 C16 16 2.5 - - 20 12 30
3)
E84AVxxx1522 - - - - - 25 10
E84AVxxx2222 - - - - - 30 10
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 - Laying system L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVxxx2512 C 6 6 1 - - 6 18
30
3)
E84AVxxx3712 C6 6 1 - - 10 16
E84AVxxx5512 C10 10 1.5 - - 10 16
30
3)
E84AVxxx7512 C10 10 1.5 - - 15 14
E84AVxxx1122 C16 16 2.5 - - 20 12
30
3)
E84AVxxx1522 C16 16 2.5 - - 25 10
E84AVxxx2222 - - - - - 30 10
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 V, tripping characteristic for example ”H”, ”K5” or CC”. The cable cross-sections apply under
the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations