26 _ Ceiling Concealed Duct(Middle Static)
Indoor Units
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or
above the listed range limits,
2. Maximum allowable voltage unbalance between phas-
es is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units Power Supply IFM Input(W)
Model Type Hz Volts Voltage Range MCA MFA kW FLA Cooling Heating
ARNU07GM1A4 M1
50 220-240
Max:264
Min:198
2.00 15 0.136 1.60 190 190
ARNU09GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU12GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU15GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU18GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU24GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU28GM2A4 M2 2.90 15 0.350 2.30 350 350
ARNU36GM2A4 M2 2.90 15 0.350 2.30 350 350
ARNU42GM2A4 M2 2.90 15 0.350 2.30 350 350
ARNU48GM3A4 M3 3.10 15 0.350 2.50 400 400
ARNU54GM3A4 M3 3.10 15 0.350 2.50 400 400
ARNU07GM1A4 M1
60 220
Max:242
Min:198
2.00 15 0.136 1.60 190 190
ARNU09GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU12GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU15GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU18GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU24GM1A4 M1 2.00 15 0.136 1.60 190 190
ARNU28GM2A4 M2 2.90 15 0.35 2.30 350 350
ARNU36GM2A4 M2 2.90 15 0.350 2.30 350 350
ARNU42GM2A4 M2 2.90 15 0.350 2.30 350 350
ARNU48GM3A4 M3 3.10 15 0.350 2.50 400 400
ARNU54GM3A4 M3 3.10 15 0.350 2.50 400 400