16 _ Ceiling Concealed Duct(Low Static)
Indoor Units
Indoor unit
7. External Static Pressure (E.S.P) & Air Flow
Setting Value
Static Pressure(mmAq(Pa))
0 (0) 1 (10) 2 (20) 3 (29) 4 (39) 5 (49)
75 6.50 - - - - -
80 7.34 6.70 - - - -
85 8.20 7.55 6.69 - - -
90 9.07 8.43 7.56 6.47 - -
95 9.96 9.32 8.45 7.36 - -
100 10.87 10.22 9.36 8.27 6.96 -
105 11.79 11.15 10.28 9.19 7.89 6.35
110 12.73 12.09 11.22 10.14 8.83 7.30
115 13.69 13.05 12.18 11.09 9.78 8.25
120 14.67 14.02 13.16 12.07 10.76 9.23
125 15.66 15.01 14.15 13.06 11.75 10.22
130 16.67 16.02 15.16 14.07 12.76 11.23
135 - - 16.18 15.10 13.79 12.26
ARNU12GL2G4, ARNU15GL2G4, ARNU18GL2G4
(Unit : CMM)
Note :
1. The above table shows the correlation between the air rates and E.S.P.
ARNU12GL2G4, ARNU15GL2G4, ARNU18GL2G4