34
MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
4/9 Configuration
Standby time 0.5 hrs
Unocc. time 0.0 hrs
Temp. occ. time 2.0 hrs
Deh. hysteresis 5 %RH
Deh. max. cool 100%
Deh. lockout Enabled
Table 17: MS8350 Conguration 4 / 9 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Standby Time
Default: 0.5 hours
Time between the moment where the PIR cover detects last movement in the area, and the time
which the Room Controller stand-by setpoints become active.
This parameter is not active when the “Door” function is used (wired or wireless).
Range: 0.5 to 24.0 hours (0.5 hour increments)
Unocc. Time (Unoccupied Time)
Default: 0.0 hours
Time between the moment where the Room Controller toggles to stand-by mode, and the time
which the Room Controller unoccupied mode and setpoints become active.
Default value of 0.0 hours disables the unoccupied timer. This prevents the Room Controller from
being able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments)
Temp. Occ. Time (Temporary
Occupancy Time)
Default value: 2 hours
The time the Room Controller stays in override mode before reverting back to unoccupied
mode. When the Room Controller is in unoccupied mode, pressing the on-screen Override icon
or closing the contact on UI17, configured as “Remote Override”, sets the Room Controller to
Override mode for defined time period, and uses the Occupied Cooling and Heating setpoints.
Range: 0.0 to 24.0 hours
Deh. hysteresis (Humidity Control
Hysteresis)
Default Value: 5 % RH
Used only if dehumidification sequence is enabled.
Range: 2 to 20% RH
Deh. Max. Cool. (Dehumidification
Maximum Cooling Limit)
Default value: 100 %
Maximum cooling valve position when dehumidification is enabled. This can be used to balance
smaller reheat loads installed in regards to the capacity of the cooling coil.
Range: 20 to 100%
Deh. Lockout (Dehumidification
Lockout)
Default value: Disabled
Enables or disables dehumidication based on central network requirements from the BAS front end.
Enabled: Dehumidification Authorized
Disabled: Dehumidification Not Authorized
Choices: Enabled or Disabled
CONFIGURATION SCREENS
MS8350 Conguration 4 / 9
MS8350 Configuration 4 / 9
Figure 27: MS8350 Conguration 4 / 9 Display.
For MS8350 Only