CONFIGURATION SCREENS
MS8650 Conguration 2 / 11
MS8650 Configuration 2 / 11
Figure 34: MS8650 Conguration 2 / 11 Display.
For MS8650 Only
Conguration Parameters Default Value Signicance and Adjustments
Fan Cont. Heat (Fan Control in Heating
Mode)
Default Value: On
On: Room Controller always controls the fan (terminal G). Valid for On or Auto fan mode.
Off: Fan (terminal G), when heating stages (terminals W1 and W2) are solicited, will not be ener-
gized. The fan is controlled by the equipment fan limit control. Valid only for Auto fan mode. On
fan mode leaves the fan always on.
For multi-stage models, fan control applies to W1 and W2.
Choices: On or Off
Fan Delay
Default Value: On
On: fan mode will leave the fan always on and extends fan operation by 60 seconds after the call
for heating or cooling ends. Valid only for Auto fan mode.
Off: fan delay not operational
Choices: On or Off
Standby Mode (Standby Mode
Configuration)
Default Value: Absolute
Standby setpoints used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied setpoints +/- Standby diff. used for standby mode.
Choices: Absolute or Offset
Standby Diff. (Standby Temperature
Differential)
Default Value: 4°F (2°C)
When Standby mode is set to “offset”, standby setpoints are calculated as follows:
Standby cool: Cool setpoint + Standby diff.
Standby heat: Heat setpoint - Standby diff.
Range: 1 to 5°F (0.5 to 2.5°C)
Power-up Delay
Default Value: 10 seconds
On initial power up of the Room Controller there is a delay before any operation is authorized
(fan, cooling or heating). This can be used to sequence the start up of multiple Room Controllers
in one location.
Range: 10 to 120 seconds
Occupancy Src (Occupancy Source)
Default Value: Motion
Motion: Occupancy status is received from a motion sensor from a wired, wireless or local PIR sensor.
Schedule: Occupancy status is determined by the schedule
Choices: Motion or Schedule
Table 27: MS8650 Conguration 2 / 11 Parameter Details.