45
User Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Conguration 3 / 11
MS8650 Configuration 3 / 11
Figure 35: MS8650 Conguration 3 / 11 Display.
For MS8650 Only
Conguration Parameters Default Value Signicance and Adjustments
Standby time
Default: 0.5 hours
Time between the moment where the PIR cover detects last movement in the area, and the time
which the Controller stand-by setpoints become active.
This parameter is not active when the “Door” function is used (wired or wireless).
Range: 0.5 to 24.0 hours (0.5 hour increments)
Unocc. Time (Unoccupied Time)
Default: 0.0 hours
Time between the moment where the Room Controller toggles to stand-by mode, and the time
which the Room Controller unoccupied mode and setpoints become active.
Default value of 0.0 hours disables the unoccupied timer. This prevents the Room Controller from be-
ing able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments)
Temp. Occ. Time (Temporary
Occupancy Time)
Default Value: 2 hours
The time the Room Controller stays in override mode before reverting back to unoccupied mode.
When the Room Controller is in unoccupied mode, pressing the on-screen Override icon or clos-
ing the contact on UI17, configured as “Remote Override”, sets the Room Controller to Override
mode for defined time period, and uses the Occupied Cooling and Heating setpoints.
Range: 0.0 to 24.0 hours
Table 28: MS8650 Conguration 3 / 11 Parameter Details.
3/11 Conf iguration
Temp. occ. tim e
Unocc. time
Standby time
2.0 hrs
0.0 hrs
0.5 hrs
Deh. lockout
Deh. hysteresis
Disabled
5 %RH
Temp. senso r
Wired