MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Conguration 3 / 11
For MS8650 Only
Table 29: MS8650 Conguration 3 / 11 Parameter Details, continued.
Conguration Parameters Default Value Signicance and Adjustments
Temp. Sensor (Room Temperature
Sensor)
Default Value: Wired
Sets the source of the indoor room temperature. This parameter allows the user to designate
either the Room Controller or any of the bound wireless devices that support temperature to act
as the source for the room temperature.
Wired: sets the thermistor connected to UI20 (RS) as the source to report room temperature.
Internal: sets the Room Controller as the source for the room temperature.
WL 1 to WL 10: sets the selected wireless ZigBee PRO device as the source for the room tem-
perature. Only one device can be selected.
The Room Controller uses the internal temperature sensor only if UI20 (RS) terminal is empty. If
a valid temperature sensor is connected to UI20 terminal, the Room Controller will automatically
disable its internal sensors (Internal, WL1 to WL10) and use the remote sensor as the control point.
Disconnecting the sensor, or if the sensor is faulty, the Room Controller will automatically re-enable its
internal temperature sensor.
Choices: Internal, Wired, WL1 to WL10
Deh. Hysteresis (Humidity Control
Hysteresis)
Default Value: 5% RH
Used only if dehumidification sequence is enabled.
Range: 2 to 20% RH
Deh. Lockout (Dehumidification
Lockout)
Default Value: Disabled
Enables or disables dehumidification based on central network requirements from the BAS front
end.
Enabled: Dehumidification Authorized
Disabled: Dehumidification Not Authorized
Choices: Enabled or Disabled