CONFIGURATION SCREENS
MS8650 Conguration 7 / 11
For MS8650 Only
MS8650 Configuration 7 / 11
Figure 39: MS8650 Conguration 7 / 11 Display.
Table 35: MS8650 Conguration 7 / 11 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Econo Min Pos (Economizer Minimum
Position)
Default Value: 0%
Minimum Outside Air damper position when the Room Controller is in Occupied, Standby or
Override mode and Fan status is ON. If the Room Controller is in Unoccupied mode and/or
the Fan is Off, Outside Air damper position goes to 0%.
Range: 0% to 100%
Econo Max Pos (Economizer Maximum
Position)
Default Value: 100%
Maximum Outside Air damper position when the Room Controller is in Occupied, Standby
or Override mode and Fan status is ON. This is valid only for Economizer, CO
2
and Airflow
functions.
Range: 0% to 100%
The Room Controller air damper position and output signal is based on a 0-10 Vdc analog actuator application. Many installations utilize 2-10 Vdc
actuators, which cannot be switched to 0-10 Vdc control logic. The following chart indicates the appropriate equivalent damper positions for use
with 2-10 Vdc actuators.
Outside air percentage 0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
Setting for 0-10 Vdc Actuator 0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
Setting for 2-10 Vdc Actuator 20% 24% 28% 32% 36% 40% 44% 48% 52% 56% 60%
Outside air percentage 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
Setting for 0-10 Vdc Actuator 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
Setting for 2-10 Vdc Actuator 64% 68% 72% 76% 80% 84% 88% 92% 96% 100%