CONFIGURATION SCREENS
MS8650 Conguration 7 / 11
For MS8650 Only
Table 36: MS8650 Conguration 7 / 11 Parameter Details, continued.
Conguration Parameters Default Value Signicance and Adjustments
Min Fresh Air (Minimum Fresh Air)
Default Value: 0 CFM
Minimum fresh air required (minimum outside airflow setpoint). Effective only in Occupied,
Standby or Override mode and Fan status is ON. If FA Range is set to value other than 0
CFM, the fresh air damper position control will be based on the Min/Max CO
2
and Min/Max
Fresh Air values.
If Room Controller is in Unoccupied mode and/or the Fan is Off, the damper position goes
to 0%.
Range: 0 to 20,000 CFM (±10 increments). The value set cannot exceed the value of FA
Range parameter.
Max Fresh Air (Maximum Fresh Air)
Default Value: 0 CFM
Maximum fresh air allowed (maximum outside airflow setpoint). Effective only in Occupied,
Standby or Override mode and Fan status is ON. If FA Range is set to value other than 0
CFM, the fresh air damper position control will be based on the Min/Max CO
2
and Min/Max
Fresh Air values.
Range: 0 to 20,000 CFM (±10 increments). The value set cannot exceed the value of FA
Range parameter.
Min CO
2
(Minimum CO
2
)
Default Value: 800 ppm
Minimum CO
2
level setpoint. Effective only in Occupied, Standby or Override mode and
Fan status is ON. The Outside Air damper modulates to maintain the CO
2
level between
“Min CO
2
” and “Max CO
2
”. If the Controller is in Unoccupied mode and/or the Fan is Off,
Outside Air damper position goes to 0%.
Range: 0 to 2,000 ppm
Max CO
2
(Maximum CO
2
)
Default Value: 1200 ppm
Maximum CO
2
level setpoint. Effective only in Occupied, Standby or Override mode and
Fan status is ON. The Outside Air damper modulates to maintain the CO
2
level between
“Min CO
2
” and “Max CO
2
”.
Range: 0 to 2,000 ppm