MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Conguration 8 / 11
For MS8650 Only
Table 37: MS8650 Conguration 8 / 11 Parameter Details.
MS8650 Configuration 8 / 11
Figure 40: MS8650 Conguration 8 / 11 Display.
Low BP
8/11 Configuration
High BP
Application
90 °F
Rooftop
Comf. or econ.
Comfort
Rev. valve
O
-12 °F
Comp. interlock
Off
Conguration Parameters Default Value Signicance and Adjustments
Application
Default Value: Rooftop
Sets Room Controller operating logic for either a Rooftop or a Heat Pump application.
If the Heat Pump Unit (HPU) does not have an O/B terminal (reversing valve), set this param-
eter to Rooftop.
Choices: Rooftop or Heat Pump
High BP (High Balance Point)
Default Value: 90°F
In Heating or Auto mode, it is the outside air temperature value at which the auxiliary heat
is cut off. If the temperature exceeds this value, only the heat pump is used to maintain the
heating setpoint.
Function enabled only if outside air temperature value is populated (not -40°F/°C). The Outdoor
Temperature value could be received from a sensor connected directly to the Room Controller
or via a BACnet front end (network).
Range: 34°F to 90°F (1.0°C to 32.0°C)
Low BP (Low Balance Point)
Default Value: -12°F
In Heating, Cooling or Auto mode, it represents the outside air temperature value at which
the heat pump operation will be cut off. If the temperature falls below this value, only the
auxiliary heat is used to maintain the heating setpoint.
Function enabled only if outside air temperature value is populated (not -40°F/°C). The Outdoor
Temperature value could be received from a sensor connected directly to the Controller or via a
BACnet front end (network).
Range: -40°F to +30°F (-40°C to -1.0°C )