MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
SERVICE VIEW SCREENS
MS8650 Service View Screen 4 / 9
MS8650 Service View Screen 4 / 9
Figure 61: MS8650 Service View Screen 4 / 9.
For MS8650 Only
Table 56: MS8650 Service View Screen 4 / 9 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Window Alarm
Read Only
Shows On if there is a Window alarm and shows Off if there is no Window alarm. This
feature is for both wired and wireless sensors.
Display Readings: On or Off
Service Alarm
Read Only
Shows On if there is a Service alarm and shows Off if there is no Service alarm.
Display Readings: On or Off
Filter Alarm
Read Only
Shows On if there is a Filter alarm and shows Off if there is no Filter alarm.
Display Readings: On or Off
Fan Lock Alarm
Read Only
Shows On if there is a problem detected on the Fan.
Display Readings: On or Off
CO
2
Alarm
Read Only
Shows On if the CO
2
level (local, wired or wireless) is higher than the “Max CO
2
” setpoint.
Display Readings: On or Off
Low Air Alarm
Read Only
Shows if the fresh air flow is lower than the “min fresh air” setpoint.
Display Readings: On or Off
Filter alarm
Window alarm
Off
Off
Off
Service alarm
Fan lock alarm
Off
4/9 Service View
CO2 alarm
Off
Low air alarm