EasyManua.ls Logo

LG PREMTBB01 - Installer Setting - Static Pressure Step Setting; Installer Setting - Fan Operation in the Cooling Mode and Thermal off Conditions

LG PREMTBB01
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
INSTALLATION INSTRUCTION
ENGLISH
INSTALLATION INSTRUCTION
83
ENGLISH
Installer Setting – Fan operation in the cooling mode and thermal off conditions
This is the function to set indoor unit fan operation at the cooling mode and thermal off condi-
tions.
Select the code value and set value for each function using
FG
button.
Press and hold
B
button for more than 3 seconds to enter the installer settings mode.
- If pressing only once briefly, it will enter the user settings mode.
Make sure to press and hold for more than 3 seconds.
Press
B
button repeatedly to move to the Settings for Fan operation in the cooling mode and ther-
mal off conditions in the menu as below.
Press
K
button to save the setting.
Press
L
button to exit.
If no button is selected for about 25 seconds after setup, it exits the setup mode automatically.
If Set button is not selected before you exit, the changes will not apply.
Code value Set value
value Fan operation
00 Fan speed Low
01 Fan off
02 Fan speed Setting value
Set value
Installer Setting – Static Pressure Step Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some models.
This is the function that static pressure of the product is divided in 11 steps for setting.
Select the code value and set value for each function using
FG
button.
Press and hold
B
button for more than 3 seconds to enter the installer settings mode.
- If pressing only once briefly, it will enter the user settings mode.
Make sure to press and hold for more than 3 seconds.
Press
B
button repeatedly to move to the Settings for Static Pressure Step in the menu as below.
Press
K
button to save the setting.
Press
L
button to exit.
If no button is selected for about 25 seconds after setup, it exits the setup mode automatically.
If Set button is not selected before you exit, the changes will not apply.
Code value Set value
Set value for static pressure step
00 : use static pressure(code 06) set value
01~ 11 : static pressure step (code 32) set value
• Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32)setting is
being used.
• For the static pressure value for each step, refer to the indoor unit in the product manual.
ENGLISH