1. Check regularly the screws at the battery connection parts, fasten it immediately if not tight.
2. Make sure that the safety equipment is complete and that the function is normal, especially that the settings of the
battery management parameters are normal.
3. Measure and record the internal temperature of the battery room.
4. Check whether the battery ports are damaged or hot, and whether the chassises and the covers are damaged
If liquid leakage and damage to the battery are found, place the battery in the nti-vitriol tank, and deal with it
according to the local regulations.
The waste lead-acid battery is dangerous waste material. It is one of the national emphases to control the waste
battery pollution. Its storage, transportation, usage and disposal must follow the national and local law and other
criterions about the dangerous waste material and the waste battery pollution prevention.
According to the related regulations, recycle the waste lead-aid battery, and other disposal methods are prohibited.
Throwing away randomly the waste lead-aid battery and other improper disposal methods can result in serious
environment pollution, which will be investigated the legal responsibility.
As the provider of the lead-acid battery, Vertiv has built perfect service network and recycle system for the waste
battery to assist users to deal with the waste battery by law. Contact Vertiv or the nearest service center for the
detailed information of the recycle system about the waste battery.
Vertiv is not liable for the environment results caused by failure to comply with the notices in this section or to use
the waste battery recycle system provided by Vertiv.
7.3 Cleaning UPS
Clean the UPS periodically, especially the ventilation holes, to ensure free airflow inside the UPS. If necessary, clean
the UPS with a vacuum cleaner. Confirm that the ventilation holes are unobstructed.
7.4 Checking UPS Status
UPS functions check procedures may cause power interruption to load!
It is recommended to check the UPS operation status once every half year.
Check the following items:
1. Check if the UPS is faulty: Is the alarm indicator on? Is the UPS giving any alarm?
2. Check if the UPS is operating in Bypass mode. Normally, the UPS operates in Normal mode; if it is operating in
Bypass mode, you should find out the reason, such as operator intervention, overload, internal fault, and so on.