Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 81
Battery
total Ah
18Ah (16/20kVA)
External battery cabinet
vgroup No.
Auto test, 0~10
Auto test
Low battery time
2~30 (min)
2
Battery replaced time
YYYY-MM-DD
HH:MM:SS
2000-01-01 0:00:00
Battery test interval
Disable, 8 weeks, 12
weeks,
16 weeks,20 weeks,26
weeks
Disable
Battery test weekday
Sunday, Monday, Tuesday,
Wednesday, Thursday,
Friday, Saturday
Wednesday
Battery test time
HH:MM:SS
0:00:00
Battery series
10kVA: 12, 16,
20
20kVA: 24, 32, 40
16 (10kVA),
32 (20kVA)
Discharge protect time
1~4320 (min)
4320
Equal charge enable
NO, YES
NO
Temperature
Compensation
Disable, Enable
Disable
Replace battery
Button
Button
Menu
Item
Setting Range
Default Setting
Outlet
Turn on outlet
Appear only when outlet off
Turn off outlet
Appear only when outlet off
Reboot outlet
Appear only when outlet off
Turn off when UPS
overload on battery
YES, NO
NO
Turn off when UPS on
battery for
0~4320 (min)
2
Turn off when backup
time less than
0~4320 (min)
0
Turn off when battery
capacity less than
20~80%
30%
Turn on when power
returns for
0~4320 (min)
MONITOR
Language
English, Chinese
English
Date
YYYY-MM-DD
2016-10-0
Time
HH:MM:SS
00:00:00
Display orientation
Auto-rotate, horizontal,
Vertical
Auto-rotate
Audible Alarm
Disable, Enable
Enable
Control port protocol
Modbus, Sensor
Sensor
Modbus address
1~128
1
IPv4 address
ddd.ddd.ddd.ddd ( 'd' is a
decimal number)
192.168.1.10
Subnet mask
255.255.255.0
Gateway address
192.168.1.1
Change settings password
The password is numeric
only and can be set from 0
to 9. The password length
is 6
111111