Chapter 5. Table of Functions
36
Code
Address
Name LCD Display Setting Range
Value
Property*
V/F
SL Ref.
07 0h1207
V/F pattern
options
V/F Pattern
0:
Linear
X/A O X
08 0h1208
Acc/dec standard
frequency
Ramp T Mode
Max
Freq
X/A O O
1 Delta Freq
09 0h1209
Time scale
settings
Time Scale
1:0.1 sec
X/A O O
10 0h120A
Input power
frequency
60/50 Hz Sel
0:60Hz X/A O O
11 0h120B
poles
Pole Number 2-48
Depend
ent on
motor
setting
X/A O O
12 0h120C
speed
Rated Slip 0-3000(Rpm) X/A O O
13 0h120D
current
Rated Curr 1.0-1000.0(A) X/A O O
14 0h120E
current
Noload Curr 0.0-1000.0(A) X/A O O
15 0h120F
voltage
Rated Volt 170-480(V) 0 X/A O O
16 0h1210 Motor efficiency Efficiency 70-100(%)
ent on
motor
setting
X/A O O
18 0h1212
display
Trim Power % 70-130(%) O/A O O
19 0h1213
voltage
AC Input Volt 170-480V
V
O/A O O
20 - Auto Tuning
Auto
Tuning
0:None X/A X O
1
type)
2
type)
3
(Rotation type)
Dependent on
motor setting
Depend
ent on
motor
setting
22 -
inductance
Lsigma X/A X O
24
7
-
constant
Tr 25-5000(ms) - X/A X O
25
7
-
scale
Ls Scale 50 ~ 150[%] 100 X/A X O