Chapter 5. Table of Functions
37
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F
SL Ref.
26
7
-
Rotor time
constant scale
Tr Scale 50 ~ 150[%] 100 X/A X O
31
7
R
egeneration
inductance scale
Ls Regen Scale 70 ~ 100[%] 80 X/A X O
41
8
0h1229 User frequency1 User Freq 1
0.00
-
Maximum
frequency(Hz)
15.00 X/A O X
42
8
0h122A
User voltage1
User Volt 1
0
-
100(%)
25
X/A
O
X
43
8
0h122B User frequency2 User Freq 2
0.00
-
0.00
-
Maximum
frequency(Hz)
30.00 X/A O X
44
8
0h122C
User voltage2
User Volt 2
0
-
100(%)
50
X/A
O
X
45
8
0h122D User frequency3 User Freq 3
0.00
-
Maximum
frequency(Hz)
45.00 X/A O X
46
8
0h122E
User voltage3
User Volt 3
0
-
100(%)
75
X/A
O
X
47
8
0h122F User frequency4 User Freq 4
0.00-Maximum
frequency(Hz)
Maximu
m
frequen
cy
X/A O X
48
8
0h1230
User voltage4
User Volt 4
0
-
100(%)
100
X/A
O
X
50
9
0h1232
Multi
-
step speed
frequency1
Step Freq-1
0.00
-
Maximum
frequency(Hz)
10.00 O/L O O
51
9
0h1233
Multi
-
step speed
frequency2
Step Freq-2
0.00
-
Maximum
frequency(Hz)
20.00 O/L O O
52
9
0h1234
Multi
-
step speed
frequency3
Step Freq-3
0.00
-
Maximum
frequency(Hz)
30.00 O/L O O
53
10
0h1235
Multi
-
step speed
frequency4
Step Freq-4
0.00
-
Maximum
frequency(Hz)
40.00 O/A O O
54
10
0h1236
Multi
-
step speed
frequency5
Step Freq-5
0.00
-
Maximum
frequency(Hz)
50.00 O/A O O
55
10
0h1237
Multi-step speed
frequency6
Step Freq-6
0.00-Maximum
frequency(Hz)
Maximu
m
frequen
cy
O/A O O
56
10
0h1238
Multi-step speed
frequency7
Step Freq-7
0.00-Maximum
frequency(Hz)
Maximu
m
frequen
cy
O/A O O
70 0h1246
Multi
-
step
acceleration
time1
Acc Time-1 0.0-600.0(s) 20.0 O/A O O
71 0h1247
Multi
-
step
deceleration
time1
Dec Time-1 0.0-600.0(s) 20.0 O/A O O
72
11
0h1248
Multi
-
step
Acc Time
-
2
0.0
-
600.0(s)
30.0
O/A
O
O
8
Displayed if either bA.07 or M2.25 is set to 2 (User V/F).
9
Displayed when an LCD keypad is in use.
10
Displayed if one of In.65-71 is set to SpeedL/M/H
11
Displayed one of In.65-71 is set to XcelL/M/H.

Other manuals for LSIS S100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS S100 Series and is the answer not in the manual?

LSIS S100 Series Specifications

General IconGeneral
BrandLSIS
ModelS100 Series
CategoryController
LanguageEnglish

Related product manuals