Chapter 5. Table of Functions
48
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F
SL
Ref.
15
34
0h150F
V1
o
utput
at
Maximum
voltage (%)
V1 Perc y2
-100.00-0.00(%) -100.00
O/A O O
16 0h1510
V1 rotation
direction change
V1 Inverting
0
No
0: No O/A O O
1
Yes
17 0h1511
V1
quantization
level
V1 Quantizing 0.00
35
, 0.04-10.00(%) 0.04 X/A O O
35
36
0h1523
V2 input
voltage
display
V2 Monitor(V) 0.00-12.00(V) 0.00 -/A O O
37
36
0h1525
V2 input filter
time constant
V2 Filter 0-10000(ms) 10 O/A O O
38
36
0h1526
V
2
Minimum
input voltage
V2 Volt x1 0.00-10.00(V) 0.00 O/A X X
39
36
0h1527
V
2
o
utput
at
Minimum voltage
(%)
V2 Perc y1 0.00-100.00(%) 0.00 O/A O O
40
36
0h1528
V
2
Maximum
input voltage
V2 Volt x2 0.00-10.00(V) 10 O/A X X
41
36
0h1529
V
2 o
utput
at
Maximum
voltage (%)
V2 Perc y2 0.00-100.00(%) 100.00
O/A O O
46
36
0h152E
V2 rotation
direction change
V2 Inverting
0
No
0:No O/A O O
1
Yes
47
36
0h152F
V2 quantization
level
V2 Quantizing 0.00
35
, 0.04- 10.00(%) 0.04 O/A O O
50
37
0h1532
I2 input
current
display
I2 Monitor (mA)
0-24(mA) 0.00 -/A O O
52
37
0h1534
I2 input filter time
constant
I2 Filter 0-10000(ms) 10 O/A O O
53
37
0h1535
I2 minimum
input current
I2 Curr x1 0.00-20.00(mA) 4.00 O/A O O
54
37
0h1536
I2
o
utput at
Minimum current
(%)
I2 Perc y1 0.00-100.00(%) 0.00 O/A O O
55
37
0h1537
I2 maximum
input current
I2 Curr x2 0.00-24.00(mA) 20.00 O/A O O
56
37
0h1538
I2
o
utput at
Maximum
current (%)
I2 Perc y2 0.00-100.00(%) 100.00
O/A O O
61
37
0h153D
Changing
rotation direction
of I2
I2 Inverting
0
No
0:No O/A O O
1 Yes
62
37
0h153E
I2 quantization
level
I2 Quantizing 0.00
35
,0.04-10.00(%) 0.04 O/A O O
65 0h1541 P1 terminal P1 Define 0 None 1:Fx X/A O O
35
Quantizing is not used when set to 0.
36
Displayed when V is selected on the analog current/voltage input circuit selection switch (SW2).
37
Displayed when I is selected on the analog current/voltage input circuit selection switch (SW2).