ECODRIVE03 SMT-02VRS Description of diagnostic letters F... and E... 3-3
DOK-ECODR3-SMT-02VRS**-WA01-EN-P
Causes:
•
The motor has been exchanged.
•
A parameter file has been loaded, but the parameter S-0-0141, Motor
type contained a motor type different from the present one.
Remedy:
Command C700 Basic Load or press the S1 button.
See also the functional description: "Automatic Execution of the Load
Default Feature".
F209 PL Load parameter default values
After replacing the firmware version, the drive displays “PL”, if the
parameters have been changed in regards to the old product. By
pressing the S1 button on the drive controller or by starting the command
“load basic parameters”, all the parameters will be erased and restored
with the default (initial) values.
Cause:
The firmware has been exchanged; the number of parameters in
comparison to the old product has changed.
Remedy:
Press S1 button on the drive controller, and all the parameters will be
erased and restored with the factory preset default values
WARNING
•
This overwrites all parameters and positioning blocks.
See also the functional description: "Basic parameter block".
F218 Amplifier overtemp. shutdown
The temperature of the amplifier’s heatsink is monitored. If the heatsink
is too hot, the drive will power down in order to protect against damage.
Cause:
1. Ambient temperature is too high. The specified performance
data are valid up to an ambient temperature of 45°C.
2. The amplifier’s heatsink is dirty.
3. Air flow is prevented by other assembly parts or the control
cabinet assembly.
4. Blower defective
5. E219: Sensor defective appears prior to shutdown of unit