3-34 Description of diagnostic letters F... and E... ECODRIVE03 SMT-02VRS
DOK-ECODR3-SMT-02VRS**-WA01-EN-P
E281 Mains fault
Cause:
The mains voltage has failed during operation for at least three mains
cycles.
In parameter P-0-0118, Power off on error mains failure and
undervoltage failure have been set as warnings.
The drive does not conduct an error reaction. If the drive continues to
operate despite the warning, an F220 Bleeder overload shutdown
could be generated.
Remedy:
Check the mains connections to ensure that they are as illustrated in the
project planning manual.
See Function Description: "Current Limit".
E386 No ready signal from supply module
Cause:
The input BbN "mains section "ready" to operateā€œ on the drive controller
is at 24V, i.e., the connected mains section does not issue a ready to
operate.
Mains failure and undervoltage errors have been set in parameter
P-0-0118, Power off on error have been set as warnings.
The drive does not conduct an error reaction. If the drive continues to
operate despite the warning, then error F220 Bleeder overload
shutdown could be generated.
Remedy:
1.) Check mains section.
2.) Check the mains section connection to input ingang BbN on the drive.
3.) If the drive is not supplied by a separate mains section, then the input
of the monitor must be switched off.
See P-0-4062, Power supply monitor
See the Function Description: "Current Limit".
E408 Invalid addressing of MDT-data container A
This warning indicates an error during the index check in the multiplex
channel. During the cyclical data exchange, the index for the access to
the list S-0-0370, Configuration list for MDT data container is
monitored as to whether it points to a non-initialized field in the list. If it
does, this warning is generated.
E409 Invalid addressing of AT-data container A
This warning indicates an error during the index check in the multiplex
channel. During the cyclical data exchange, the index for the access to
the list S-0-0371, Configuration list for the AT data container is
monitored as to, whether it points to a non-initialized field in the list. If it
does, this warning is generated.
See also the functional description: "Checking the Indices"