Mannesmann ecodrive03 - C220 Feedback 1 Initializing Error; C221 Feedback 2 Initializing Error

Mannesmann ecodrive03
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECODRIVE03 SMT-02VRS Description of Diagnostic Letters B..., C..., D... and A... 4-15
DOK-ECODR3-SMT-02VRS**-WA01-EN-P
Remedy:
For 1. Check the measurement system cable.
For 2. Exchange the measurement system.
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C220 Feedback 1 initializing error
A number of tests are performed when the motor encoder is initialized. An
error was detected during this process. This error may be:
•
Error while reading the angle rectification data
•
Error while copying the angle rectification data
•
Interruption of communication with the encoder
•
Assembly error with the position of an initialization track
•
Error while reading the analog signal of an initialization track
•
Error in the pointer length of the analog signal of an initialization track
•
Invalid offset between the high and low resolution track
•
Error in the measuring system micro-controller
Cause:
1. Defective motor feedback cable
2. Defective motor feedback
3. Defective measurement system interface
Remedy:
For 1. Check the motor feedback cable.
For 2. Exchange the motor.
For 3. Exchange the measuring system interface, if it is a module, or the
complete drive controller.
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C221 Feedback 2 initializing error
Several checks are performed during the initialization of an optional
encoder. An error has been detected during this process. This error may
be:
•
Error while reading the angle rectification data
• Error while copying the angle rectification data
• Interruption of communication with the encoder
• Assembly error with the position of an initialization track
• Error while reading the analog signal of an initialization track
• Error in the pointer length of the analog signal of an initialization track
• Invalid offset between the high and low resolution track
• Error in the measuring system micro-controller
• With DAG 1.2: external 24V set for SSI interface