ECODRIVE03 SMT-02VRS Description of Diagnostic Letters B..., C..., D... and A... 4-19
DOK-ECODR3-SMT-02VRS**-WA01-EN-P
C500 Reset class 1 diagnostic, error reset
The command for clearing errors, S-0-0099, C500 Reset class 1
diagnostic was activated by the control system in use. All drive internal
errors are cleared. But before that happens, the cause of the error must
have been cleared.
See also the functional description: "Clearing Error"
C600 Drive controlled homing procedure command
Command S-0-0148, C600 Drive controlled homing procedure
command has been activated by the control system in use.
See also the functional description: "Drive-Controlled Homing"
C601 Homing only possible with drive enable
Cause:
The controller enabling signal was not active when the program was
started. This is not permitted.
Remedy:
1. Switch on the controller enable signal.
2. Start the command again.
See also the functional description: "Functions of the Control During
Drive-Controlled Homing"
C602 Distance home switch - reference mark erroneous
Cause:
The evaluation of the homing switch has been activated. The distance
between the positive homing switch edge and the reference mark that
shall be interpreted is outside the valid range.
Remedy:
Read the value from the S-0-0298, Reference cam shift by ... parameter
and enter it in the S-0-0299, Home switch offset parameter.
See also the functional description: "Connection of the Home switch"
C604 Homing of absolute encoder not possible
Cause:
If, with absolute encoder, the homing command was called without having
done the command P-0-0012, Set absolute measuring before, the
homing command is cancelled with this error.
If the encoder had been referenced with the "Set absolute measuring“,
then the homing command would give you a possibility to trigger a
positioning move to the reference point.